Add to Cart
HVH Piston Series Solenoid Valve Of Refrigeration / Air Conditioning System,For Refrigeration Unit
Description:
* HVH piston type solenoid valve is a twice open-type solenoid valve to be suitable to one-way flow.
* HVH piston type solenoid valve is used on the liquid, air suction and not vapor pipes of the refrigeration, cold storage and air conditioning facilities.
* The coil of varies voltages is available for Model HVH piston type solenoid valve with a universal valve body.
* HVH piston type solenoid valve could be supplied in whole or in split means the valve body and coil could be supplied separately.
Specifications:
Model | Size | △P(bar) | Max Operating Pressure(bar) | Kv(㎥/h) | |
Weld Connection | Min. | MOPD LiquidMOP | |||
HVH3-2T | 1/4ODF | 0.05 | 31 | 45 | 0.27 |
HVH8-3T | 3/8ODF | 0.05 | 31 | 45 | 0.8 |
HVH10-4T | 1/2ODF | 0.05 | 31 | 45 | 1.4 |
HVH10-5T | 5/8ODF | 0.05 | 31 | 45 | 1.9 |
HVH15-6T | 3/4ODF | 0.05 | 31 | 45 | 2.6 |
HVH10-7T | 7/8ODF | 0.05 | 31 | 45 | 2.8 |
1) Kv value: The flow rate (m³/h) of water of density 1t/m³ passing through the solenoid valve with the pressure differential of 100 KPa.
2) The MOPD of gaseous medium is about 1 bar higher than that of liquid.
Model | Nominal Refrigerating Capacity kW | ||||||||
Liquid | Air Suction | Hot Vapor | |||||||
R22/R407C | R134a | R404A/R507 | R22/R407C | R134a | R404A/R507 | R22/R407C | R134a | R404A/R507 | |
HVH3 | 5.40 | 5.00 | 3.80 | --- | --- | --- | 2.50 | 2.00 | 2.00 |
HVH8 | 16.10 | 14.80 | 11.20 | 1.80 | 1.30 | 1.60 | 7.40 | 5.90 | 6.00 |
HVH10 | 38.20 | 35.30 | 26.70 | 4.30 | 3.10 | 3.90 | 17.50 | 13.90 | 14.30 |
HVH15 | 52.30 | 48.30 | 36.500 | 5.90 | 4.20 | 5.30 | 24.00 | 19.00 | 19.60 |
The working condition the nominal refrigerating capacity of liquid and air suction is as follows:
Evaporation Temperature: te = -10℃;
Liquid Temperature before Valve: t1 = +25℃;
Pressure Drop after Solenoid Valve: △P = 15KPa
The working condition the nominal refrigerating capacity of hot vapor is as follows:
Condensation Temperature: tc = +40℃;
Pressure Drop after Solenoid Valve: △P = 80KPa;
Hot Vapor Temperature: th = +65℃;
Liquid Refrigerant Overcooding: △t = 4K
Technical Parameters:
Applicable Refrigerants: | HCFC or HFC(Customer apecified) |
Applicable Medium Temperature: | -30℃~+140℃ |
Application Ambient Temperature of Solenoid | -40℃~+65℃ |
Standard Voltage of Solenoid | AC 380V,AC 220V/50Hz(Customer design is available) |
Allowable Voltage Fluctuation for Solenoid | +10%~15% |